Reeling & Trailing Cable Mechanical & Thermal Characteristics
A. Cable Minimum Bending Radius :
-
Installation condition 1.1/1.1kV 6D 3.3/3.3~33/33kV 8D For dispatch drum barrel 6D 8D For fixed bend 4D 6D For free flexing 6D 10D For permanently repeating reeling 10D 12D For passing over sheaves 10D 15D - For XLPE and Paper insulated HV cables, bending radii is 18D (during installation) / 12D (installed).
B. Cable Maximum Pulling Tension :
-
For trailing the cable 20N/mm² of the total cross-sectional area of phase conductor For dragging the cable calculated by T = L*W*f*10, where T is the pulling tension, L is the length of cable to be pulled
(m), W is the weight of the cable (kg/m), f is the friction coefficient (usually take as 0.5)
C. Temperature :
- Maximum continuous conductor temperature: +90℃
- Minimum continuous conductor temperature: -25℃